Products

Sump Test System

The Sump Test System (STS) is designed specifically to test containment for leaks. Up to four containments can be leak-tested simultaneously with accurate compliance test results available in just 15 minutes.

features

Highlights

  • Designed to deliver cost-effective environmental compliance test data.
  • Easily transported in two supplied carrying cases.
  • Easily set-up and programmed with site-specific data and sump identification before a test. Site and test data can also be saved to a laptop.
  • Laptop interface optional using System Sentinel™ Tech Software.
  • Accommodates up to four probes for testing of up to four spill containers, dispenser sumps, or tank sumps simultaneously.
  • Uses magnetostrictive probe technology for unparalleled accuracy and reliable results.
  • Highly accurate leak test detects level changes greater than 0.002 inches during the fifteen minute test.
  • Provides accurate test fluid levels for each sump monitored.
  • Automatically prints out passed or failed test reports in just fifteen minutes after starting a leak test. Printer included.
  • Shows the date and time of the test, test fluid levels, and the leak test results on sump leak test reports.
  • Additional sump leak test reports can also be printed at the console before other tests are completed.

Specs

  • Operating temperature:
  • Console: 32° to 122 °F (0° to 50 °C)
  • Leak test probes: -40° to 140 °F (-40° to 60 °C)
  • Storage temperature:
  • Console: -4° to 140 °F (-20° to 60° C)
  • Leak test probes: -40° to 158 °F (-40° to 70 °C)
  • Intrinsic safety rating:
  • Leak test probes: Class 1, Div. 1, Group D
  • Carry case weight and dimensions:
  • Console: 33 lbs. (15 kg), 24″ × 19″ × 8½” (62 cm × 49 cm × 22 cm)
  • Leak test probes: 30 lbs. (13.5 kg), 38″ × 18″ × 6″ (97 cm × 45 cm × 16 cm)
  • Number of sumps monitored:
  • Console: 4
  • Leak test probes: 1
  • Applicable liquids:
  • Leak test probes – testing solution.
  • Level units:
  • Console – inches.
  • Display type and size:
  • Console – alphanumeric LCD,
  • 2 lines of 40 characters.
  • Printer type:
  • Console – 24 column thermal printer.
  • Power requirements:
  • Console – 115 VAC, 50 Watts, 6′ power cord with 3 prong plug supplied.
  • Leak test probes – 50′ cable supplied.

Order Info

Model Description
TS-STS-2K Sump test system with two probes
TS-STS-3K Sump test system with three probes
TS-STS-4K Sump test system with four probes